Low Voltage Switchgear

Type of test/Properties measured/Range of measurement
Standard specifications/ Equipment/Techniques used
Verification of Temperature rise, up to 5000 A, 3 phase AC IEC 61439-1 Edition 2   2011-08
IEC 61439-2  Edition 2   2011-08
Verification of dielectric properties
a. Power Frequency withstand voltage  up to 4.5 kV
b. Impulse withstand voltage up to  20 kV peak c. Insulation resistance test – Up to 5 kV / 950 GΩ
IEC 61439-1  Edition 2   2011-08
IEC 61439-2  Edition 2   2011-08
Verification of clearance and creepage distances IEC 61439-1  Edition 2   2011-08
IEC 61439-2  Edition 2   2011-08
Verification of degree of protection Up to IP55 IEC 60529    Edition 2.2 2013-08
IEC 61439-1 Edition 2   2011-08
IEC 61439-2 Edition 2   2011-08
Verification of strength of materials and parts (Lifting) Up to 5000 kg IEC 61439-1 Edition 2   2011-08
IEC 61439-2  Edition 2   2011-08
Verification of mechanical operation IEC 61439-1 Edition 2   2011-08
IEC 61439-2 Edition 2   2011-08
Electrical continuity of earthed metallic parts test IEC 61439-1 Edition 2   2011-08